Title: Dewatering of sanitary installations located under building basement

Authors: MATUSIEWICZ, W.

Keywords: foundation, excavation, excessive rise in ground water level, sanitary installation, geotechnical parameters, drainage, infiltration of into the soil, channel installation

Abstract: Under floor plumbing technology system of grease food catering facilities after 10 years of operation has been soiled and deformation. After digging out, it turned out that the pipe and backfill soils are flooded. Geotechnical studies have shown that the cause of flooding are rain water and water from subsurface as well as from fine sand layer. They infiltrated the foundation backfill in precinct. Soils adjacent to the sewage system are loamy sands and sandy clays in plastic firm and soft plastic states. Microcracks occur due to settling of internal walls, of the building. Sewage was qualified for replacement. In order to prevent re-undercuts drainage was proposed. It will be protected from clogging the duallayer filter reaching to the bottom floor. Two structures have also been proposed to install server pipes in the channel technology. First system was proposed in cohesive soils with two-layer filter for drain and single-layer filter for channel, however in sandy soils second system as only-layer filter for drain

APA style references: Matusiewicz, W. (2015). Dewatering of sanitary installations located under building basement. Scientific Review Engineering and Environmental Sciences, 24 (3), 286-300.

APA style citation in text: The first time citation in text: (Matusiewicz, 2015), next citation: (Matusiewicz, 2015)

Chicago style references: Matusiewicz, Władysław. "Dewatering of sanitary installations located under building basement." Scientific Review Engineering and Environmental Sciences, 69 ser., vol. 24, no 3, (2015): 286-300.

Chicago style citation in text: (Matusiewicz 2015)

Bibtxt style references: @article{Matusiewicz_2015_PNIKS, author={Matusiewicz, Władysław}, title={Dewatering of sanitary installations located under building basement.}, journal={Scientific Review Engineering and Environmental Sciences}, URL={http://iks_pn.sggw.pl/PN69/A7/art7.pdf}, year={2015}, volume={24 (3)}, number={69}, pages={286-300}}